Bg

Low-Voltage Switchgear Assembly: Definition & Key Classifications​

2025-06-10 09:19

Core Definition:
A Low-Voltage Switchgear Assembly comprises one or more low-voltage switching devices, integrated with associated control, measurement, signaling, protection, and regulation equipment. The manufacturer completes all internal electrical and mechanical connections, assembling the components into a structurally complete unit within an enclosure.

Classification by Design Verification Level:

  1. Fully Type-Tested Assembly (TTA):

    • Conforms to a verified design series.

    • Demonstrates full compliance with IEC 61439.1 through comprehensive type testing.

    • Exhibits no deviations from the tested prototype that could impact performance.

  2. Partially Type-Tested Assembly (PTTA):

    • Integrates both type-tested components and non-type-tested elements.

    • Non-type-tested sections derive from validated designs (e.g., via calculation-based extensions of tested configurations).

Classification by Construction:

  • Fixed Mounting Design: Power Center (PC) or Motor Control Center (MCC) circuits installed without withdrawal capability.

  • Withdrawable/Draw-Out Design: PC or MCC circuit breakers designed for safe isolation and removal while the assembly remains energized.

Classification by Primary Function:

  • Power Distribution (PCC - Power Control Center): Feeder panels distributing primary power.

  • Motor Control (MCC - Motor Control Center): Panels dedicated to starting, stopping, and protecting electric motors.

  • Power Factor Correction: Capacitor banks for reactive power compensation.

Key Assembly Components:

  1. Enclosure: Structural chassis, supporting framework, and internal mounting hardware.

  2. Busbars: Low-impedance conductors distributing power to multiple circuits.

  3. Functional Unit: Integrated assembly of electrical and mechanical components performing a specific function (e.g., incoming feeder unit, outgoing circuit unit).

Internal Partitioning (Segregation Types - IEC 61439):

  • Type 1: No internal barriers between functional zones.

  • Type 2: Segregation between busbars and functional units only.

  • Type 3:

    • Segregation between busbars and functional units.

    • Segregation between adjacent functional units.

    • Segregation between functional units and outgoing terminals/cable connections.

  • Type 4 (Highest Segregation):

    • Segregation between busbars and functional units.

    • Segregation between adjacent functional units.

    • Segregation between functional units and outgoing terminals/cable connections.

    • Segregation between outgoing terminals/cable connections of adjacent units.

  • Common Partitioned Compartments: Busbar chamber (horizontal/vertical), Functional unit compartment, Cable termination chamber, Auxiliary (control) compartment.

Critical Technical Parameters:

  • Rated Operational Current (Ie): Typically matches the main incoming circuit breaker rating.

  • Rated Operational Voltage (Ue) / Rated Insulation Voltage (Ui): e.g., 690V / 1000V.

  • Termination Types: Cable entry/exit methods (top/bottom/side, glands, bushings).

  • Rated Short-Time Withstand Current (Icw): RMS current the assembly can safely carry for a specified time (typically 1 second).

  • Degree of Internal Separation: Defined by Segregation Type (1-4).

  • Ingress Protection (IP) Rating: Enclosure protection against solids/liquids.

  • Installation: Mounting location (indoor/outdoor) and method (floor-standing, wall-mount).

  • Dimensions: External HxWxD dimensions (impacting floor space).

  • Finishing: Coating type, color (RAL codes).

  • Earthing System: Design and specifications.

  • Busbar Parameters:

    • Rated Current (determines cross-section/material).

    • Rated Short-Time Withstand Current (Icw).

    • Rated Peak Withstand Current (Ipk = Typically 2.2 x Icw).

    • Surface Treatment: Tin plating, silver plating, nickel plating for reduced resistance/corrosion protection.

Functional Unit Connection Types:

  • Fixed: Main circuit connections can only be made/broken when the assembly is isolated/de-energized.

  • Removable (Disconnectable): Can be safely disconnected/isolated from the main circuit while the assembly is live. Includes "Connect" and "Disconnect/Remove" positions.

  • Withdrawable: Can be safely isolated, tested, disconnected, and fully removed while the assembly is live. Includes "Connect," "Test," "Disconnect/Isolate," and "Remove" positions.

IP Code (Ingress Protection) Breakdown:

  • First Digit - Solid Particle Protection:

    • 0: No protection

    • 1: >50mm objects

    • 2: >12.5mm objects

    • 3: >2.5mm objects

    • 4: >1.0mm objects

    • 5: Dust protected (limited ingress)

    • 6: Dust tight

  • Second Digit - Liquid Ingress Protection:

    • 0: No protection

    • 1: Vertically falling drops

    • 2: Vertically falling drops (tilted up to 15°)

    • 3: Spraying water (up to 60° from vertical)

    • 4: Splashing water (from any direction)

    • 5: Low-pressure water jets (from any direction)

    • 6: Powerful water jets / Heavy seas

    • 7: Temporary immersion (1m depth for 30 min)

    • 8: Continuous immersion (specified depth/time)


Get the latest price? We'll respond as soon as possible(within 12 hours)
This field is required
This field is required
Required and valid email address
This field is required
This field is required
For a better browsing experience, we recommend that you use Chrome, Firefox, Safari and Edge browsers.